The Borri E8031/E8033 Emergency Central System (ECS) UPS has been designed in accordance with EN 50171 standards making them an ideal system for emergency lighting, fire and life safety applications.
Overview
As per the EN 50171 regulation, these central power systems (CPS) come with a 10 year battery life expectancy, deep discharge protection, 120% overload capacity and are housed in an IP20 metal enclosure.
Key Features
Additional Features
-
Batteries with 10 years life expectancy
-
Acid proof battery cabinets and racks
-
Battery polarity reversal protection
-
Deep discharge protection
-
Short circuit protection
-
Battery charger recharges battery to 80% autonomy in 12 hours
-
Battery charger compensation
-
IP20 metal enclosure as per EN60598-1
-
Green Conversion technology, providing high efficiency and UPS components life extension
-
Compact transformer free design for small footprint
-
Easy access for fast maintenance and low MTTR
-
AO EO mode kit
-
Isolation transformer
-
Separate rectifier and bypass input for E8000 ECS 3-phase output models
-
Parallel kit
-
Backfeed protection (standard with 10, 15 and 20 kVA ratings)
Technical Specification
WARRANTY | 3 Year Parts |
RATING KVA | 10 / 15 / 20 / 30 / 40 / 50 |
MAX EM LIGHTING LOAD | 9 / 13.5 / 18 / 27 / 36 / 45 |
DIMENSIONS (WxDxH) | 450W x 670D x 1200H |
WEIGHT | 100 / 110 / 110 / 140 / 140 / 170 |
INPUT PHASE | Three Phase + Neutral |
INPUT VOLTAGE | 400VAC |
INPUT VOLTAGE TOLERANCE RANGE | -20% / +15% |
INPUT FREQUENCY | 50/60Hz |
INPUT FREQUENCY TOLERANCE RANGE | 45-65Hz |
OUTPUT OUTPUT PHASE | Three Phase + Neutral |
OUTPUT POWER FACTOR | 1 |
OUTPUT WAVEFORM | Sinewave |
OUTPUT VOLTAGE | 380/400/415VAC |
OUTPUT FREQUENCY | 50-60Hz (Sync with mains ±2Hz) |
OUTPUT EFFICIENCY | ≥95% (AC-AC) / >98% (Eco mode / changeover mode) / 97% (DC-AC) |
BATTERY RUNTIME | Dependent on battery capacity |
BATTERY DC VOLTAGE | 720VDC or 744VDC |
BATTERY CHARGE CAPACITY | TBC (Borri yet to complete tech. specification) |
MECHANICAL AC OUTLETS | Hardwired |
OPERATING TEMPERATURE TOLERANCE | 0-40°C |
STORAGE TEMPERATURE TOLERANCE | -10 - +70°C |
RELATIVE HUMIDITY | <95% (non-condensing) |
OPERATING ALTITUDE TOLERANCE | <1000m |
COMMUNICATION | USB, RS232 and Modbus |
OPTIONAL COMMS | SNMP / VFC |
PARALLEL | Up to 6 (others on request) |
FUNCTIONS | EPO, Expandable Battery, Mimic LCD and keyboard, Temperature compensated charging |
Resources
Product Brochure
Related products
30kVA - 160kVA
Monolithic - CPSS
Designed in compliance with EN 50171 standards, ideal for emergency and life safety systems
Borri Ingenio ECS (Emergency Central System) is a central power system (CPS) that has been designed in compliance with the international EN 50171 regulation. The CPS features online double conversion and a slimline design thanks to the transformer free technology.
3kVA - 80kVA
Modular - CPSS
Designed in accordance with EN 50171 standards, ideal for emergency and life safety systems
The Legrand Trimod MCS series is a modular centralised power system (CPS) designed in accordance with EN 50171 regulation making them the ideal solution for backing up buildings subject to fire safety standards and to power emergency lighting systems.