Borri E8031/E8033 ECS

Legrand

The Borri E8031/E8033 Emergency Central System (ECS) UPS has been designed in accordance with EN 50171 standards making them an ideal system for emergency lighting, fire and life safety applications.

Overview

As per the EN 50171 regulation, these central power systems (CPS) come with a 10 year battery life expectancy, deep discharge protection, 120% overload capacity and are housed in an IP20 metal enclosure.

Additional Features

  • Batteries with 10 years life expectancy
  • Acid proof battery cabinets and racks
  • Battery polarity reversal protection
  • Deep discharge protection
  • Short circuit protection
  • Battery charger recharges battery to 80% autonomy in 12 hours
  • Battery charger compensation
  • IP20 metal enclosure as per EN60598-1
  • Green Conversion technology, providing high efficiency and UPS components life extension
  • Compact transformer free design for small footprint
  • Easy access for fast maintenance and low MTTR
  • AO EO mode kit
  • Isolation transformer
  • Separate rectifier and bypass input for E8000 ECS 3-phase output models
  • Parallel kit
  • Backfeed protection (standard with 10, 15 and 20 kVA ratings)

Technical Specification

WARRANTY 3 Year Parts
RATING KVA 10 / 15 / 20 / 30 / 40 / 50
MAX EM LIGHTING LOAD 9 / 13.5 / 18 / 27 / 36 / 45
DIMENSIONS (WxDxH) 450W x 670D x 1200H
WEIGHT 100 / 110 / 110 / 140 / 140 / 170
INPUT PHASE Three Phase + Neutral
INPUT VOLTAGE 400VAC
INPUT VOLTAGE TOLERANCE RANGE -20% / +15%
INPUT FREQUENCY 50/60Hz
INPUT FREQUENCY TOLERANCE RANGE 45-65Hz
OUTPUT OUTPUT PHASE Three Phase + Neutral
OUTPUT POWER FACTOR 1
OUTPUT WAVEFORM Sinewave
OUTPUT VOLTAGE 380/400/415VAC
OUTPUT FREQUENCY 50-60Hz (Sync with mains ±2Hz)
OUTPUT EFFICIENCY ≥95% (AC-AC) / >98% (Eco mode / changeover mode) / 97% (DC-AC)
BATTERY RUNTIME Dependent on battery capacity
BATTERY DC VOLTAGE 720VDC or 744VDC
BATTERY CHARGE CAPACITY TBC (Borri yet to complete tech. specification)
MECHANICAL AC OUTLETS Hardwired
OPERATING TEMPERATURE TOLERANCE 0-40°C
STORAGE TEMPERATURE TOLERANCE -10 - +70°C
RELATIVE HUMIDITY <95% (non-condensing)
OPERATING ALTITUDE TOLERANCE <1000m
COMMUNICATION USB, RS232 and Modbus
OPTIONAL COMMS SNMP / VFC
PARALLEL Up to 6 (others on request)
FUNCTIONS EPO, Expandable Battery, Mimic LCD and keyboard, Temperature compensated charging

Resources

Product Brochure

Related products

Borri Ingenio ECS

30kVA - 160kVA

Monolithic - CPSS

Designed in compliance with EN 50171 standards, ideal for emergency and life safety systems

Borri Ingenio ECS (Emergency Central System) is a central power system (CPS) that has been designed in compliance with the international EN 50171 regulation. The CPS features online double conversion and a slimline design thanks to the transformer free technology.

Legrand Trimod MCS

3kVA - 80kVA

Modular - CPSS

Designed in accordance with EN 50171 standards, ideal for emergency and life safety systems

The Legrand Trimod MCS series is a modular centralised power system (CPS) designed in accordance with EN 50171 regulation making them the ideal solution for backing up buildings subject to fire safety standards and to power emergency lighting systems.